FBCDZ Series Explosion-Proof Extractive Counter-Rotating Axial Flow Main Ventilation Fan

FBCDZ Series Explosion-Proof Extractive Counter-Rotating Axial Flow Main Ventilation Fan

FBCDZ Series Explosion-Proof Counter-Rotating Mine Main Ventilation Fan is designed for main ventilation systems in large coal mines. It adopts a counter-rotating axial flow structure, direct motor-impeller connection, enclosed motor protection and adjustable blade angle. With high static pressure efficiency, reversible airflow and stable operation under different mine ventilation network resistance conditions, it is suitable for long-term continuous coal mine main ventilation.
Send Inquiry
Description
Coal Mine Main Ventilation Fan | Counter-Rotating Explosion-Proof Axial Flow Design

FBCDZ Explosion-Proof Counter-Rotating Mine Main Ventilation Fan

FBCDZ Series Explosion-Proof Counter-Rotating Mine Main Ventilation Fan is designed for main ventilation systems in large and medium-sized coal mines. It adopts a two-stage counter-rotating axial flow structure, direct motor-impeller connection, enclosed motor protection and adjustable blade angle for stable mine ventilation under different network resistance conditions.

Structure
Counter-Rotating
Fan Function
Mine Main Fan
Static Efficiency
Up to 86%+
Reverse Airflow
Up to 60%

Counter-Rotating Design for Mine Main Ventilation

FBCDZ series is developed for coal mine ventilation networks where main fans must handle larger airflow, higher resistance adaptability and long-term continuous operation. Compared with ordinary single-stage axial mine fans, the counter-rotating structure uses two impellers rotating in opposite directions to improve pressure adaptability and reduce intermediate guide vane losses.

This series is suitable for surface extractive ventilation in large and medium-sized coal mines. It can also be considered for mine ventilation projects where explosion-proof protection, high efficiency, reverse airflow capability and stable performance under changing resistance conditions are required.

Core Structural Advantages

Two-Stage Counter-Rotating Impellers

The two impellers rotate in opposite directions, reducing guide vane losses and improving fan efficiency under mine ventilation network resistance.

Direct Motor-Impeller Connection

Direct connection avoids transmission device failure risks and reduces energy loss, helping improve overall installed fan efficiency.

Enclosed Motor Protection

Motors are installed inside pressure-resistant sealed covers in the main air duct, helping isolate the motor from gas-containing airflow while supporting cooling and positive pressure protection.

Reversible Airflow

The fan can reverse airflow by reverse rotation. Reverse airflow can reach about 60% of normal airflow, reducing the need for a separate reverse air duct.

Adjustable Blade Angle

Blade installation angle can be adjusted according to mine production and ventilation demand, improving adaptability to different operating stages.

Stable No-Hump Performance Curve

The fan is designed for stable operation under different mine network resistance conditions, helping support continuous main ventilation operation.

Reference Technical Parameters

The following data is for preliminary model comparison. Final selection should be confirmed according to mine ventilation network resistance, required airflow, static pressure, gas condition, reverse airflow requirement, motor configuration and installation layout.

Item
Reference Data
Fan Series
FBCDZ Series, formerly BDK62 Series
Fan Type
Explosion-proof extractive counter-rotating axial flow main ventilation fan
Main Application
Large and medium-sized coal mine main ventilation systems
Impeller Structure
Two-stage counter-rotating impellers
Drive Structure
Direct motor-impeller connection
Static Pressure Efficiency
Up to 86%+ under suitable operating conditions
Reverse Airflow
About 60% of normal airflow

Representative Model Parameters

Series
Machine No.
Installed Power
Air Volume
Air Pressure
Speed
FBCDZ(B)-4
No.11
2×45 kW
17–33 m³/s
830–2670 Pa
1480
FBCDZ(B)-4
No.14
2×110 kW
32–59 m³/s
1300–4400 Pa
1480
FBCDZ(A)-6
No.16
2×55 kW
23–53 m³/s
450–1970 Pa
980
FBCDZ(A)-6
No.19
2×110 kW
41–91 m³/s
600–2780 Pa
980
FBCDZ(B)-6
No.20
2×220 kW
55–119 m³/s
1170–4100 Pa
980
FBCDZ(B)-6
No.22
2×355 kW
72–160 m³/s
1400–4900 Pa
980
FBCDZ(B)-8
No.18
2×75 kW
31–67 m³/s
520–1900 Pa
740
FBCDZ(B)-8
No.24
2×250 kW
72–155 m³/s
1000–3400 Pa
740
FBCDZ(B)-12
No.38
2×800 kW
190–413 m³/s
1100–3800 Pa
480

Motor Isolation and Positive Pressure Protection

The motor is installed inside a sealed cover in the main air duct. The sealed cover has pressure resistance and helps isolate the motor from gas-containing airflow in the fan passage.

Streamlined air ducts connect the sealed cover with outside fresh air, allowing fresh air to enter the cover and helping maintain positive pressure during operation. This structure supports explosion-proof operation and motor cooling in mine ventilation applications.

Application Scenarios

Coal Mine Main Ventilation Large Mine Surface Fan Station Explosion-Proof Extractive Ventilation High-Resistance Mine Network Mine Reverse Airflow System Long-Term Continuous Operation

Information Required for Fan Selection

To recommend a suitable FBCDZ mine main fan model, please provide the following working conditions. These details help match fan performance with the actual mine ventilation network.

Required airflow volume
Static pressure or total pressure
Mine ventilation network resistance
Gas condition and safety requirement
Reverse airflow requirement
Motor power and voltage
Fan station layout
Blade angle adjustment requirement

Need an FBCDZ Mine Main Fan Selection?

Send us your airflow, pressure, mine ventilation network resistance, gas condition and fan station layout. Qiyue Fan can help recommend a suitable explosion-proof counter-rotating mine main ventilation fan.

Manager Zhao
Industrial Ventilation Fan Supplier
SHANDONG QIYUE FAN CO., LTD.
Tel / WeChat / WhatsApp: +86 15653305981  |  Email: sales@qiyuefan.com

Hot Tags: fbcdz series explosion-proof extractive counter-rotating axial flow main ventilation fan, China fbcdz series explosion-proof extractive counter-rotating axial flow main ventilation fan manufacturers, suppliers, factory

Send Inquiry