T40 Axial Flow Fan

T40 Axial Flow Fan

T40 axial flow fan is designed for general ventilation and air exchange in factories, warehouses, offices and buildings.
The series covers No.2.5 to No.10, with 4-blade impellers and blade-angle settings of 15°, 20°, 25°, 30° and 35°.
Airflow range: 565–48,200 m³/h; total pressure: 31–473 Pa; standard medium temperature: ≤45°C.
Suitable for free-air ventilation, duct ventilation and general industrial exhaust applications.
Send Inquiry
Description
General Industrial Axial Flow Fan
T40 Axial Flow Fan
 

The T40 axial flow fan is designed for general ventilation and air exchange in factories, warehouses, offices and residential buildings. It can also support heat dissipation and long duct ventilation where additional airflow and pressure are required.

The series covers No.2.5 to No.10 with a four-blade impeller and five blade-angle settings from 15° to 35°. Maximum conveyed-medium temperature is 45°C.

 
T40 axial flow fan with four blade impeller for industrial ventilation
Fan Sizes
No.2.5–10
Impeller
4 Blades
Medium
≤45°C
Fan Sizes
No.2.5–10
Airflow
565–48,200
m³/h
Total Pressure
31–473 Pa
Blade Angles
15°–35°
Motor Power
0.025–7.5
kW
 
T40 Configuration

Four-Blade Axial Fan with Five Blade-Angle Settings

The T40 series uses a four-blade axial impeller. Blade-angle settings of 15°, 20°, 25°, 30° and 35° provide multiple operating points within the same fan size.

Different fan sizes use 2900, 1450 or 960 r/min operating speeds according to the original performance data. Selection should be based on the required airflow and total pressure rather than fan diameter alone.

01
4-Blade Impeller
Standard T40 performance data is based on four blades.
02
Five Angle Settings
15°, 20°, 25°, 30° and 35° operating configurations.
03
Multiple Speeds
2900, 1450 and 960 r/min depending on fan size.
04
≤45°C Medium
Standard operating-medium temperature limit from the original T40 data.
 
Performance Range

T40 Performance by Fan Size

The ranges below combine the listed blade-angle and speed conditions in the original T40 performance tables.

Size
Speed r/min
Airflow m³/h
Pressure Pa
Motor kW
2.5
1450 / 2900
565–2,272
31–184
0.025–0.18
3
1450 / 2900
976–3,931
45–266
0.09–0.55
3.5
1450 / 2900
1,552–6,239
62–363
0.06–1.1
4
1450 / 2900
2,318–9,310
80–473
0.25–2.2
5
960 / 1450
2,992–9,090
54–184
0.25–0.75
6
960 / 1450
5,159–15,700
79–267
0.75–2.2
7
960 / 1450
8,201–24,998
108–363
0.75–4
8
960 / 1450
12,301–37,520
140–473
1.1–7.5
9
960
17,399–31,500
177–263
1.5–4
10
960
24,001–48,200
220–323
2.2–7.5
Selection note: The same T40 fan size can produce different airflow and pressure at different blade angles. Selection should be based on the actual operating point.
 
Blade Angle Example

No.10 Performance at 960 r/min

The No.10 data clearly shows how increasing blade angle changes airflow, pressure and motor requirement.

Angle
Pressure Pa
Airflow m³/h
Shaft kW
Motor kW
15°
220
24,001
2.150
2.2
20°
243
30,701
2.910
3
25°
246
39,337
3.680
4
30°
262
42,700
4.260
5.5
35°
323
48,200
6.150
7.5
 
Technical Drawing

T40 Outline & Installation Drawing

The T40 drawing provides front and side views of the fan casing, four-blade impeller arrangement, motor position, mounting base, flange and the dimensional references used for installation.

T40 axial flow fan outline and installation technical drawing
01
No.2.5–10
The dimensional schedule covers the complete T40 size range.
02
Dimensions in mm
A–K values in the table below are specified in millimetres.
03
Installation Interface
Check casing, flange and mounting-base dimensions before installation.
04
Production Drawing
Final project dimensions should be confirmed before fabrication or installation.
 
Installation Dimensions

T40 Dimensions - No.2.5 to No.10

Dimensions below correspond to the A–K references shown in the technical drawing. All values are in millimetres.

No.
A
B
C
D
E
F
G
H
I
J
K
2.5
253
275
296
300
118
144
110
163
82
175
225
3
303
331
353
360
141
171
183
195
104
210
270
3.5
354
382
404
420
165
200
162
228
128
245
315
4
404
432
454
480
188
227
184
260
150
280
360
5
505
537
565
600
235
283
231
325
191
350
450
6
606
638
666
720
282
339
278
390
234
420
540
7
707
739
767
840
330
396
325
455
271
490
630
8
808
846
872
960
376
453
368
520
298
560
720
9
909
958
994
1080
423
509
415
585
345
630
810
10
1010
1059
1095
1200
470
565
462
650
382
700
900
Final interface and installation dimensions should be confirmed against the production drawing before installation.
 
Installation

Free-Air or Duct Ventilation Installation

01
General Ventilation
Suitable for general air exchange in industrial and building ventilation.
02
Free-Air Arrangement
The original product description allows use as a free fan when the casing is removed.
03
Long Duct Systems
Multiple fans can be arranged at intervals in longer exhaust ducts where additional duct pressure is required.
04
Temperature Check
Standard medium temperature must not exceed 45°C.
 
Applications

Typical T40 Ventilation Applications

 

Factories

General workshop ventilation and air exchange.

 

Warehouses

Air circulation and ventilation in storage buildings.

 

Offices & Buildings

General building ventilation where a conventional axial fan is suitable.

 

Heat Dissipation

Air movement to support general heat dissipation.

 

Exhaust Ducts

Longer exhaust ducts requiring axial airflow and additional system pressure.

 
Model Selection

What to Send for T40 Fan Selection

A fan should not be selected only from duct diameter. Send the required duty point and installation conditions so the fan size, speed and blade angle can be checked together.

Required airflow (m³/h)
Required total pressure (Pa)
Duct or free-air installation
Conveyed medium and temperature
Power supply voltage / frequency / phase
Installation space or existing fan dimensions
Quantity and destination country
 
FAQ

T40 Axial Flow Fan FAQ

01

What is the airflow range of the T40 axial flow fan?

Across the No.2.5–10 series and listed operating conditions, airflow ranges from 565 to 48,200 m³/h.

02

How many blades does the T40 fan use?

The original T40 performance data is based on a four-blade impeller.

03

Which blade angles are available?

The performance tables list 15°, 20°, 25°, 30° and 35° blade-angle settings.

04

What is the maximum gas temperature?

The standard conveyed-medium temperature should not exceed 45°C.

05

Can the T40 fan be installed in a duct?

Yes. The original product description allows use in exhaust duct systems and also describes interval series installation in longer ducts when additional duct pressure is required.

06

Can QIYUE FAN supply motors for different voltages and frequencies?

Motor configuration can be reviewed according to the project power supply. Send the required voltage, frequency and phase with the RFQ.

T40 Fan Selection

Send Your Required Airflow and Pressure

QIYUE FAN can review the T40 fan size, speed, blade angle and motor configuration according to your project data.