9-19 High Pressure Centrifugal Fan

9-19 High Pressure Centrifugal Fan

9-19 high pressure centrifugal fan for forced air supply, boiler draft, combustion support, material conveying and industrial equipment airflow systems. Designed for higher pressure airflow requirements under suitable working conditions. Model selection can be reviewed according to airflow, pressure, medium, temperature, motor power and installation direction.
Send Inquiry
Description
PRESSURE-FIRST · HIGH-RESISTANCE AIRFLOW
9-19 High Pressure Centrifugal Fan
 

The 9-19 high pressure centrifugal fan is designed for industrial air systems where pressure demand and system resistance are the primary selection factors. Typical duties include forced air supply, boiler forced draft, combustion support, pneumatic conveying and process equipment air delivery.

Smaller models use A-type direct drive arrangements, while larger models use D-type coupling drive arrangements. Final selection should be based on airflow and total pressure at the same operating point, then checked against speed, motor load, medium condition, rotation, discharge angle and installation interface.

QIYUE 9-19 high pressure centrifugal fan for industrial forced air systems
SELECTION LOGIC
Pressure First
Confirm required airflow at the actual system resistance before final model selection.
PRODUCT POSITION

High Pressure Fan for Forced Air and High-Resistance Systems

The 9-19 series is intended for systems where ordinary ventilation fans may not provide sufficient pressure to overcome duct resistance, equipment resistance, filters, dampers, bends or process restrictions.

For replacement projects, an existing nameplate, motor plate, performance curve and general arrangement drawing can help identify the original fan configuration. However, motor power or model number alone should not be used as the final selection basis.

MODEL RANGE
4A–16D
Small A-type to larger D-type models.
DRIVE ARRANGEMENT
A / D
A type No.4–6.3 · D type No.7.1–16.
CATALOGUE SPEEDS
960–2900
r/min depending on size and duty point.
DISCHARGE POSITIONS
0°–225°
0° / 45° / 90° / 135° / 180° / 225°.
PERFORMANCE DATA

Representative 9-19 Performance Parameters

Representative catalogue ranges are shown to establish the available duty level. The complete catalogue contains multiple operating points for each fan size.

Model Drive Speed
r/min
Catalogue Airflow
m³/h
Total Pressure
Pa
Listed Motor Options
kW
4A A 2900 824–1,704 3,253–3,665 2.2–3
5A A 2900 1,610–3,488 5,080–5,768 5.5–11
6.3A A 2900 3,220–6,978 8,148–9,265 15–30
7.1D D 2900 4,610–9,988 10,426–11,868 37–55
10D D 1450 6,440–15,455 4,958–5,941 22–37
12.5D D 960 8,327–19,985 3,377–4,043 18.5–37
Performance note: The figures above summarize selected catalogue operating points and are not a single guaranteed duty point. Final fan size, speed and motor power must be checked against the required airflow and total pressure at the same operating condition.
PERFORMANCE SELECTION

Match the Fan Curve to the Actual System Resistance

Long ducts, elbows, filters, dampers, furnace passages and process equipment all create pressure loss. A high-pressure fan should therefore be selected from the required operating point rather than from motor power or fan number alone.

01 · AIRFLOW
Required volume flow under the real process condition.
02 · PRESSURE
Required total pressure or calculated system resistance.
03 · SPEED
Matched with fan diameter, curve and duty point.
04 · MOTOR LOAD
Motor capacity follows the selected working point.
APPLICATIONS

Typical 9-19 High Pressure Fan Applications

Boiler Forced Draft
Forced combustion air where pressure is required to overcome furnace and duct resistance.
Pneumatic Conveying
Pressure-oriented airflow source for reviewed industrial conveying systems.
Equipment Air Supply
Process equipment requiring stable forced airflow against significant resistance.
Combustion Support
Controlled process air delivery where combustion stability depends on both pressure and airflow.
High-Resistance Duct Systems
Long ducts, multiple bends, filters, dampers and equipment pressure losses.
Replacement Projects
Replacement review using existing operating data, nameplate, motor data, curve and installation interface.
Dust-handling boundary: For direct dust-laden or abrasive airflow, particle concentration, hardness, pre-separation and fan position should be reviewed before selection. Do not select the fan for abrasive dust service from the model name alone.
OUTLINE & INSTALLATION DIMENSIONS

9-19 Engineering Drawings and Representative Dimensions

Read the engineering drawing first, then use the matching table directly below it. The drawing defines each dimension code; the tables provide representative 9-19 catalogue values in millimetres.

No.4A–6.3A · A Type
ENGINEERING DRAWING
9-19 9-26 No.4A to 6.3A high pressure centrifugal fan outline and installation dimensions
9-19 A TYPE · REPRESENTATIVE DATA

Representative A-Type Installation Dimensions

Dimension codes correspond directly to the drawing above. Values are in mm except hole and bolt specifications.

Model D1 D2 D3 A1 A2 A3 E G M N Inlet / Outlet Holes Foundation Bolt
4A Φ180 Φ205 Φ230 128 160 182 100 599 718 420 8×Φ7 / 14×Φ7 M12×300
5A Φ224 Φ254 Φ284 160 192 214 126 743 868 500 8×Φ7 / 14×Φ7 M12×300
6.3A Φ280 Φ320 Φ360 202 236 258 157 936 1085 620 8×Φ10 / 14×Φ7 M16×400
Representative models are shown to keep the page readable. The catalogue also includes No.4.5A and No.5.6A dimensional rows.
No.7.1D–16D · D Type
ENGINEERING DRAWING
9-19 9-26 No.7.1D to 16D high pressure centrifugal fan outline and installation dimensions
9-19 D TYPE · REPRESENTATIVE DATA

Representative D-Type Installation Dimensions

Representative No.7.1D, No.10D and No.16D values show the dimensional progression across the larger D-type range.

Model D1 D2 D3 A1 A2 A3 E G L M H Inlet / Outlet Holes Foundation Bolts
7.1D Φ315 Φ355 Φ395 227 270 293 177 1051 1230 1278 280 8×Φ10 / 14×Φ10 M24×630 / M20×500
10D Φ450 Φ500 Φ550 320 360 386 250 1472 1317 1748 280 8×Φ12 / 18×Φ10 M24×630 / M20×500
16D Φ710 Φ770 Φ830 512 574 621 400 2351 2091 2735 500 16×Φ12 / 24×Φ12 M36×1000 / M30×800
Foundation bolt format: D-type rows show bearing-seat foundation bolt / casing foundation bolt. Motor foundation bolts depend on the selected motor and should be confirmed with the final production drawing.
FINAL GA CONFIRMATION
Catalogue dimensions are used for preliminary engineering review. Before manufacturing, confirm the exact fan number, motor configuration, rotation direction, discharge angle, foundation arrangement and project interface. Final production GA drawing controls.
RFQ INPUTS

Information Needed for 9-19 Fan Selection

AIR DUTY
Airflow + Pressure
Required airflow in m³/h and total or static pressure in Pa.
MEDIUM
Temperature + Gas Condition
Temperature, gas composition, dust content and any abrasive or corrosive condition.
ELECTRICAL
Voltage + Frequency
Motor voltage, frequency, phase and any special electrical requirement.
INSTALLATION
Rotation + Outlet Angle
Rotation direction, discharge angle, orientation and available installation space.
REPLACEMENT
Existing Fan Information
Fan nameplate, motor plate, old GA drawing, performance curve and interface dimensions.
COMMERCIAL
Quantity + Destination
Required quantity, project destination and requested delivery schedule.
FAQ

9-19 High Pressure Centrifugal Fan FAQ

What is the 9-19 high pressure centrifugal fan mainly used for?

Typical applications include forced air supply, boiler forced draft, combustion support, pneumatic conveying and industrial process systems with relatively high resistance.

How should the correct 9-19 model be selected?

Confirm airflow and required pressure at the same operating point first, then check fan size, speed, motor load, medium condition, rotation direction, discharge angle and installation arrangement.

What is the difference between A-type and D-type 9-19 fans?

The No.4–6.3 group uses A-type arrangements, while No.7.1–16 uses D-type coupling-drive arrangements. Their mechanical layouts, foundations and installation dimensions are different.

Why are only representative performance and dimension rows shown?

The full catalogue contains many operating points and dimensional rows. Representative data makes the product page easier to evaluate while retaining the key engineering values needed for preliminary selection.

Can QIYUE FAN review replacement of an existing 9-19 or similar fan?

Yes. Send the existing fan nameplate, motor data, airflow and pressure, performance curve if available, rotation, outlet angle and installation drawing or interface dimensions.

Are the catalogue dimensions sufficient for final manufacturing?

No. Catalogue dimensions are for preliminary engineering reference. The final production drawing should be confirmed after fan size, motor, rotation direction, outlet angle and project interface are finalized.

QIYUE FAN · PROJECT SELECTION
Send Your 9-19 Fan Working Point
Airflow · Pressure · Temperature · Medium · Voltage · Rotation · Outlet Angle · Quantity