Y10-21 Industrial Boiler Induced Draft Fan is designed for flue-gas extraction in industrial boiler systems.
The series covers No.8 and No.9 configurations with reference airflow of 4,215–16,252 m³/h, total pressure of 2,303–3,312 Pa and motor power of 7.5–22 kW.
C-type belt drive and D-type coupling drive arrangements are available. Final selection should consider airflow, pressure, flue-gas temperature, dust condition, outlet direction, voltage and frequency.
Y10-21 is a single-inlet centrifugal induced draft fan developed for industrial boiler flue-gas extraction. No.8 and No.9 configurations cover reference duties for 2-ton and 4-ton industrial boilers, with C-type belt drive and D-type coupling drive arrangements available.
Y10-21 is a single-suction centrifugal induced draft fan used on industrial boiler flue-gas systems. The fan is installed downstream of the boiler and gas-cleaning equipment to overcome resistance through the furnace, heat-transfer surfaces, dust collector and flue system.
The catalog configuration covers No.8 and No.9 fans at 1450 rpm, with separate reference duties for smaller and larger industrial boiler systems.
02 / Boiler Reference Duty
No.8 and No.9 Reference Configurations
No.8
2-Ton Boiler
4,215–11,115 m³/h
2,303–2,509 Pa
No.9
4-Ton Boiler
6,000–16,252 m³/h
3,038–3,312 Pa
03 / Drive Arrangement
C-Type Belt Drive or D-Type Coupling Drive
C Type
V-Belt Drive
Motor power is transmitted through V-belts and pulleys, allowing a separate motor position and practical maintenance access.
D Type
Coupling Drive
Motor and fan shaft are connected through a coupling for direct mechanical transmission.
04 / Catalog Performance
Y10-21 No.8 Performance
Reference speed: 1450 rpm.
POINT
AIRFLOW m³/h
TOTAL PRESSURE Pa
SHAFT POWER kW
MOTOR
1
4,215
2,303
3.83
7.5 kW
2
5,400
2,391
4.75
7.5 kW
3
6,736
2,460
5.85
7.5 kW
4
7,536
2,489
6.53
7.5 kW
5
8,148
2,499
7.22
7.5 kW
6
9,598
2,509
8.81
11 kW
7
10,281
2,499
9.65
11 kW
8
11,115
2,509
10.76
11 kW
Y10-21 No.9 Performance
Reference speed: 1450 rpm.
POINT
AIRFLOW m³/h
TOTAL PRESSURE Pa
MOTOR
1
6,000
3,038
18.5 kW
2
7,775
3,165
18.5 kW
3
9,590
3,254
18.5 kW
4
10,730
3,283
18.5 kW
5
11,600
3,303
18.5 kW
6
13,665
3,312
18.5 kW
7
14,642
3,303
18.5 kW
8
16,252
3,224
22 kW
05 / Flue-Gas Condition
Temperature and Dust Must Be Checked Together
No.8 Reference
Catalog reference medium temperature: up to approximately 220°C.
No.9 Reference
Catalog reference medium temperature: approximately 200°C.
Dust Collection
The catalog requires a dust-removal device with efficiency of at least 85% upstream of the induced draft fan.
Gas temperature changes density and therefore affects pressure, shaft power and motor selection. Always provide the actual flue-gas temperature when requesting selection.
06 / No.9D Installation Dimensions
Reference No.9D Interface Dimensions
D1
D2
D3
INLET HOLES
A1
A2
A3
A4
A5
A6
450
500
550
8 × Ø12
506
560
595
180
234
269
Overall Dimensions - No.9D
E
F
G
K
L
M
H
378
601
1403
668
1459
1791
280
Dimensions are in millimetres and correspond to the catalog No.9D reference arrangement. Final fabrication and foundation work should follow the approved project GA drawing.
07 / Outlet Orientation
Multiple Discharge Directions
0°
45°
90°
135°
180°
225°
Confirm the required rotation and discharge angle before manufacturing because outlet direction affects foundation position, duct connection and maintenance clearance.
08 / Selection Information
What to Send for Y10-21 Selection
01 · Airflow - Required operating airflow in m³/h.
02 · Pressure - Required total or static pressure and its measurement basis.
03 · Gas Temperature - Normal and maximum flue-gas temperature.
The catalog data supplied for this series covers No.8 and No.9 configurations.
What airflow range is available?
The reference catalog range is approximately 4,215 to 16,252 m³/h.
What pressure does Y10-21 provide?
Reference catalog duty points cover approximately 2,303 to 3,312 Pa total pressure.
What is the difference between C and D drive?
C-type uses V-belt transmission, while D-type uses a coupling between the fan and motor shafts.
Is a dust collector required upstream?
The original catalog specifies an upstream dust-removal device with efficiency not lower than 85% to reduce dust entering the fan and improve service life.
Can the discharge direction be specified?
Yes. The catalog provides multiple outlet orientations including 0°, 45°, 90°, 135°, 180° and 225°. Confirm the required direction before manufacturing.
Y10-21 Boiler ID Fan Selection
Send the Actual Boiler and Flue-Gas Duty.
Airflow · Pressure · Gas Temperature · Dust Condition · Drive Arrangement · Outlet Angle · Voltage · Frequency · Quantity