Y10-21 Industrial Boiler Induced Draft Fan is designed for flue-gas extraction in industrial boiler systems.
The series covers No.8 and No.9 configurations with reference airflow of 4,215–16,252 m³/h, total pressure of 2,303–3,312 Pa and motor power of 7.5–22 kW.
C-type belt drive and D-type coupling drive arrangements are available. Final selection should consider airflow, pressure, flue-gas temperature, dust condition, outlet direction, voltage and frequency.
Y10-21 is a single-inlet centrifugal induced draft fan for industrial boiler flue-gas extraction. The product manual provides No.8 and No.9 reference configurations at 1450 rpm, with C-type belt drive and D-type coupling drive arrangements.
Manual Basis
No.8 / No.9
1450 rpm
C / D Drive
≤250°C
01 / Engineering Overview
Industrial Boiler Flue-Gas Extraction
Y10-21 is a single-inlet centrifugal induced draft fan used in industrial boiler flue-gas systems. It works on the exhaust side of the boiler system and is selected to overcome resistance from the furnace, heat-transfer surfaces, dust-removal equipment, flue duct and discharge route.
The product manual provides No.8 and No.9 reference configurations at 1450 rpm. Final fan selection must still be based on the actual operating airflow, pressure, temperature and system resistance.
Product Role
Y10-21 belongs to the boiler induced-draft route and should not be selected only from boiler tonnage or motor power.
02 / Boiler Reference Duty
No.8 and No.9 Reference Configurations
No.8
2 t/h Reference
4,215–11,115 m³/h
2,303–2,509 Pa
No.9
4 t/h Reference
6,000–16,252 m³/h
3,038–3,312 Pa
Manual reference only: 2 t/h and 4 t/h are reference boiler duties in the product manual. Final selection must use the real operating point.
03 / Drive Arrangement
C-Type Belt Drive and D-Type Coupling Drive
C TYPE
V-Belt Drive
Power is transmitted through V-belts and pulleys. The motor is separated from the fan shaft and the arrangement provides practical access for belt and motor maintenance.
D TYPE
Coupling Drive
The motor and fan shaft are connected through a coupling for direct mechanical transmission.
04 / Manual Structure
Main Structural Features from the Product Manual
Impeller Material
16Mn steel construction is specified in the product manual.
Impeller Blades
24 blades in total: 12 long blades and 12 short blades.
Blade Direction
Forward-curved blade arrangement according to the manual description.
Bearing Housing
Water-cooled bearing housing is used to reduce thermal load in hot flue-gas service.
05 / Product Manual Performance
Y10-21 No.8 Performance
Reference speed: 1450 rpm.
POINT
AIRFLOW
PRESSURE
SHAFT POWER
MOTOR
1
4,215
2,303
3.83 kW
7.5 kW
2
5,400
2,391
4.75 kW
7.5 kW
3
6,736
2,460
5.85 kW
7.5 kW
4
7,536
2,489
6.53 kW
7.5 kW
5
8,148
2,499
7.22 kW
7.5 kW
6
9,598
2,509
8.81 kW
11 kW
7
10,281
2,499
9.65 kW
11 kW
8
11,115
2,509
10.76 kW
11 kW
Y10-21 No.9 Performance
Reference speed: 1450 rpm.
POINT
AIRFLOW
PRESSURE
MOTOR
1
6,000
3,038
18.5 kW
2
7,775
3,165
18.5 kW
3
9,590
3,254
18.5 kW
4
10,730
3,283
18.5 kW
5
11,600
3,303
18.5 kW
6
13,665
3,312
18.5 kW
7
14,642
3,303
18.5 kW
8
16,252
3,224
22 kW
Performance data source: values above follow the supplied Y10-21 product manual. Final fan selection must be checked against the actual project duty.
06 / Flue-Gas Condition
Temperature and Dust Conditions
Maximum Medium Temperature
The product manual specifies that the conveyed medium temperature should not exceed 250°C.
Dust Removal Requirement
The manual requires upstream dust-removal equipment with efficiency not lower than 85%.
Actual flue-gas temperature must still be provided during selection because gas density changes with temperature and affects fan pressure and absorbed power.
07 / Engineering Drawing
Y10-21 No.9D Installation and Overall Dimensions
The drawing below is based on the supplied product manual and includes the No.9D installation interface, overall dimensions and outlet orientation references.
Engineering note: use the approved project GA drawing for final foundation construction, duct fabrication and installation. The drawing shown here is a manual reference drawing.
08 / Outlet Orientation
Available Discharge Directions
0°
45°
90°
135°
180°
225°
Confirm rotation and discharge angle before manufacturing because outlet direction affects the foundation, duct connection and maintenance space.
09 / Selection Information
What to Send for Y10-21 Selection
01 / Airflow
Required operating airflow in m³/h.
02 / Pressure
Required total or static pressure and measurement basis.
03 / Temperature
Normal and maximum flue-gas temperature.
04 / Dust Condition
Dust-removal equipment, efficiency and expected dust loading.